Universal circuit breaker

ZHHW1 SERIES UNIVERSAL CIRCUIT BREAKER

ZHHW1 SERIES UNIVERSAL CIRCUIT BREAKER

Universal circuit breaker
Product Introduction:

product overviewZHHW1 series intelligent universal
circuit breakers hereinafter referred to as circuit breakers suitable for ac 50 Hz rated voltage to 660

product details

product overview

ZHHW1 series intelligent universal      circuit breakers (hereinafter referred to as circuit breakers), suitable for ac 50 Hz, rated voltage to 660      V(690V)and below, rated current 630 A~6300A in the power distribution network, it is used to distribute electric      energy and protect lines and power equipment from overload, undervoltage, short circuit, single-phase grounding      and other faults. the circuit breaker has intelligent protection functions and precise selective protection, which      can improve power supply reliability and avoid unnecessary power outages. at the same time, it has an open      communication interface and can perform "four remotes" to meet the requirements of the control center and      automation system. the circuit breaker has a pulse withstand voltage of 8000 at an altitude of 2000 meters.      V(different altitudes are corrected according to standards, the maximum does not exceed 12,000 V)。this circuit      breaker can be used as an isolator without intelligent controller and sensor, and is marked asimage.png

circuit breaker complies with GB14048.2《      low voltage switchgear and control equipment low voltage circuit breaking special and IEC60947-2《 "low-voltage      switchgear and control equipment" and other standards.


normal operating conditions and        installation conditions

ambient air temperature

the upper limit value does not exceed +40℃,the lower limit      value is not less than -5 ℃,24h the average does not exceed +35℃。

note: the lower limit is -10 ℃or -25 ℃working conditions,      the user should declare with the company; the upper limit value exceeds +40℃or the lower limit value is lower than      -10 ℃or -25 ℃for working conditions, users should negotiate with our company. the altitude of the installation      site does not exceed 2000 m.


atmospheric conditions

the relative humidity of the atmosphere in the surrounding      air is +40℃it does not exceed 50%, and can have higher relative humidity at lower temperatures. the monthly      average maximum relative humidity of the wettest month is 90%, and the average minimum temperature of the month is      +25℃,and take into account condensation on the product surface that occurs due to temperature changes. if the      requirements exceed the specified requirements, please consult with the company.


protection level: IP30

pollution level: Ⅲ

usage categories: B class or A kind


installation category

rated working voltage 660 V(690V)and below circuit breakers      and undervoltage releases, primary coils of power transformers are used for installation categories Ⅳ;the      installation categories of auxiliary circuits and control circuits are Ⅲ。


installation conditions

the circuit breaker should be installed in accordance with      the requirements of this manual. the vertical inclination of the circuit breaker shall not exceed 5 degrees (the      inclination of the mining circuit breaker shall not exceed 15 degrees).


model description


3

4

5

6

M/H

3/4

universal circuit breaker

shell frame grade: 2000

rated current: 400 A

630A

800A

1000A

1250A

1600A

2000A

shell frame grade: 3200

rated current: 2000 A

2500A

2900A

3200A

shell frame grade: 4000

rated current: 3200 A

3600A

4000A

shell frame grade: 6300

rated current: 4000 A

5000A

6300A

breaking ability level

(KA)

number of poles

note: frame grade: 2000 type, rated current: 630 A、      breaking capacity: M type, number of poles: 3 poles, should be determined as: AD3-630M/3.


product classification

according to installation method: fixed type, drawer      type

divided according to the number of poles: three poles, four      poles

according to operation mode: electric operation, manual      operation (for inspection and maintenance )


smart controller performance

intelligent controllers are divided into: H type (for      communication), M type (ordinary intelligent type), L type (economical type);

it has overload long delay inverse time limit, short delay      inverse time limit, definite time limit and instantaneous functions. the required protection characteristics can      be set by the user:

single-phase ground fault protection function:

display function: setting current display, operating      current display, voltage display of each phase (voltage display should be mentioned when ordering:

alarm function: overload alarm:

self-check function: overheating self-check, microcomputer      self-diagnosis;

test function: test the action characteristics of the      controller.


simple structure

circuit breaker front indication

0.jpg


technical parameters

0.jpg


undervoltage release

the undervoltage release is composed of a release coil and      a control unit.

the actions of the undervoltage release are divided into      two types: clockwise action and delayed action:

the delay time of the undervoltage delay release is      generally divided into four types: 1, 2, 3, and 5. the delay accuracy ±10%。

image.png

rated working voltage Ue(V)

AC400A

AC230

operating voltage (V)

(0.35-0.7)Ue

reliable closing voltage (V)

(0.85-1.1)Ue

reliable non-closing voltage (V)

≤0.35Ue

power consumption

12VA

note: in thunderstorm-prone areas or in power grids with      unstable power supply voltage, it is recommended to use an undervoltage release with a delay to prevent the      circuit breaker from tripping due to a short-term voltage drop. the delay time is generally 1 S、2S、3S、5S available      for user selection.


shunt tripper

can be operated remotely to open the circuit breaker

image.png

rated control power supply voltage Us(V)

AC400

AC230

DC220

DC110

operating voltage (V)

(0.7~1.1)Us

instantaneous current

0.7

1.3

1.3

2.4

the breaking time is not greater than

no more than 30 ms


closing electromagnet

after the energy storage is completed, the closing      electromagnet can instantly release the energy storage spring force of the operating mechanism to quickly close      the circuit breaker.

image.png

rated control power supply voltage Us(V)

AC400

AC230

DC220

DC110

operating voltage (V)

(0.85~1.1)Us

instantaneous current (A)

0.7

1.3

1.3

2.4

closing time

no more than 30 ms


electric operating mechanism

the circuit breaker has motor energy storage and automatic      re-storage functions;

the circuit breaker can also be manually stored.

image.png

rated control power supply voltage Us(V)

AC400

AC230

DC220

DC110

operating voltage (V)

(0.85~1.1)Us

power consumption

85VA、110VA、150VA

85VA、110VA、150VA

energy storage time

no more than 5 s


auxiliary switch

rating

image.png

rated voltage Ue(V)

agreed heating current Ith

rated control capacity

AC

230

6

300VA

400

DC

220

60W

110

note: the standard type of auxiliary switch is 4 sets of      change-over contacts, and the special type is 4 normally open and 4 normally closed, 6 normally open and 2      normally closed, 2 normally open and 6 normally closed, 3 normally open and 3 normally closed.


mechanical        accessories

“"open" locking device

“the "open" locking device can lock the disconnect button      of the circuit breaker (drawer type or fixed type) in the pressed position. at this time, the circuit breaker      cannot be closed;

after user selection, the factory provides locks and      keys

1、a circuit breaker with an independent lock and      key;

2、two circuit breakers come with two identical locks and      one key;

3、three circuit breakers come with three identical locks      and two identical keys.

image.png


drawer circuit breaker "disengaged" position        locking padlock

when the drawer-type circuit breaker is in the      "disconnected" position, the locking lever can be pulled out and locked with a padlock. after locking, the circuit      breaker cannot be moved to the "test" or "connected" position;

padlocks are provided by the user.

image.png

circuit breaker phase partition

the phase partition strengthens the insulation between      busbars and is an optional part of the circuit breaker, which can be configured by the user when needed.

image.png


steel cable interlocking of two flat circuit        breakers or twostacklinkage interlock for installing circuit breaker

0.jpg


santaistacklinkage interlock for installing        withdrawable circuit breaker

0.jpg


installation dimensions and overall dimensions of        withdrawable circuit breaker (Inm=2000A three poles and four poles )

0.jpg


fixed circuit breaker installation dimensions and        overall dimensions (Inm-2000A three poles and four poles )

0.jpg


installation dimensions and overall dimensions of        withdrawable circuit breaker (Inm=3200A three poles and four poles )

0.jpg


fixed circuit breaker installation dimensions and        overall dimensions (nm=3200A three poles and four poles )

0.jpg


installation dimensions and overall dimensions of        withdrawable circuit breaker (Inm=4000A three poles )

0.jpg


fixed circuit breaker installation dimensions and        overall dimensions (Inm=4000A three poles )

0.jpg


installation dimensions and overall dimensions of        withdrawable circuit breaker (lnm=4000A four poles )

0.jpg


installation dimensions and overall dimensions of        withdrawable circuit breaker (Inm=5000A three poles )

0.jpg


installation dimensions and overall dimensions of        withdrawable circuit breaker (Inm=6300A three poles )

0.jpg


circuit breaker door frame hole        size

0.jpg